Product Code
ME-10000-WPRU
Phase
Single phase with ground
Capacity
10000 VA / 8000 VA
Input
Voltage Range
Low Line Transfer
176 VAC Ā± 3% @ 100% load 110 VAC Ā± 3% @ 50% load
Low Line Comeback
186 VAC Ā± 3% @ 100% load 120 VAC Ā± 3% @ 50% load
High Line Transfer
300 VAC Ā± 3%
High Line Comeback
290 VAC Ā± 3%
Frequency Range
46~54 Hz or 56~64 Hz
Power Factor
ā§ 0.99 @ 100%load
Output
Output Voltage
208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
Ā± 1%
Frequency Range (Batt. Mode)
50 Hz Ā± 0.1 Hz or 60 Hz Ā± 0.1 Hz
Current Crest Ratio
3:1
Harmonic Distortion
ā¦ 3 % THD (Linear Load) ā¦ 5 % THD (Non-linear Load)
Transfer Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
Zero
Waveform (Batt. Mode)
Pure Sinewave
Efficiency
AC Mode
93%
Battery Mode
91%
Battery
Battery Type
12 V / 9 Ah
Numbers
16
Typical Recharge Time
9 hours recover to 90% capacity
Charging Current (max.)
1.0 A / 2.0 A (adjustable)
Charging Voltage
218.4 VDC Ā±1%
Indicators
LCD Panel
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
Physical
Dimension, D x W x H (mm)
UPS: 580 x 483 x 133 [3U] Battery: 588 x 438 x 133 [3U]
Net Weight (kgs)
UPS: 18 Battery: 51
Environment
Humidity
0-95 % RH @ 0- 40Ā°C (non-condensing)
Noise Level
Less than 58dB @ 1 Meter
Management
Smart RS-232/USB
Supports Windows 2000/2003/XP/Vista/2008, Windowsļ²7/8, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
There are no reviews yet.