Product Code
ME-1000-WPRU
Phase
Single phase with ground
Capacity
1000 VA / 800 W
Input
Voltage Range
Low Line Transfer
160 VAC/140 VAC/120 VAC/110 VAC Ā± 5% (Ambient Temp.<35Ā°C) (based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Comeback
175 VAC /155 VAC/ 135 VAC /125 VACĀ± 5 % (Ambient Temp.<35Ā°C) (based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
High Line Transfer
300 VAC Ā± 5 %
High Line Comeback
290 VAC Ā± 5 %
Frequency Range
40Hz ~ 70 Hz
Power Factor
ā§ 0.99 @ nominal voltage
Output
Output Voltage
200/208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
Ā± 1%
Frequency Range (Batt. Mode)
50 Hz Ā± 0.25 Hz or 60Hz Ā± 0.3 Hz
Current Crest Ratio
3:1
Harmonic Distortion
ā¦ 3 % THD (Linear Load), ā¦ 6% THD (non-linear load)
Transfer Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
4 ms (Typical)
Waveform (Batt. Mode)
Pure Sinewave
Efficiency
AC Mode
88%
Battery Mode
83%
Battery
Battery Type
12 V / 9 Ah
Numbers
2
Typical Recharge Time
4 hours recover to 90% capacity
Charging Voltage
27.4 VDC Ā± 1%
Indicators
LCD Panel
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
Physical
Dimension, D x W x H (mm)
310 x 483 x 88 [2U]
Net Weight (kgs)
12
Environment
Humidity
20-90 % RH @ 0- 40Ā°C (non-condensing)
Noise Level
Less than 50dB @ 1 Meter
Management
Smart RS-232/USB
Supports Windows 2000/2003/XP/Vista/2008, Windowsļ²7/8, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser